Coal Flow Monitoring System
General
Information
Triple
5's Coal Flow System measures concentration of coal dust in boiler
supply pipes.
With this information, the system detects pluggage and measures
balance of coal dust between pipes.
The
installation is non-invasive, using two surface mount transducers
attached with adhesive to the outside of a coal pipe near the nozzle.
The maximum number of pipes per system is 96.
The
system uses a stand-alone Data Logging Computer, or may be added to an
existing Triple 5 Leak Detection system.
Accuracy increases when the plant supplies mill data, such as
coal flow, air flow, air temperature, and boiler MW.
Installation
Each
pipe uses two transducers mounted 90 degrees apart and bonded directly
to the pipe. A small
stainless steel box, held in place with a pipe strap, protects each
transducer.
Transducers
connect to any 8 channel Processor module with shielded-twisted-pair (STP)
wire. The Processor module
mounts in a NEMA box within 50 ft of any four pipes.
The system supports as many as 24 Processor modules (192
transducers, 96 pipes).
Processor
modules daisy-chain together with a four pair STP cable.
The STP cable terminates to an Interface module or Remote Power
Box near the Processor. The
Interface module supplies 24 VDC to power the Processor modules near the
boiler.
The
Triple 5 Data Logger connects to the plant computer via Modbus.
In the works is an Ethernet connection.
Wireless Installation
The
components on the boiler communicate with the Processor module via
RS-422 serial link. This
link can be hard wired STP or wireless spread-spectrum link.
When doing wireless, the system needs a Power/RF box near the
boiler for Processor and Radio power.
The Power/RF box requires local 120 VAC power.
In
place of the wireless link, you may use a fiber optic cable.
System Cost
- Less than $2,500 per pipe for system components.
|